logo

Standards Manage Your Business

We Manage Your Standards

IEC

IEC 62271-102:2018 (EN-FR)

High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches

Standard Details

IEC 62271-102:2018 applies to alternating current disconnectors and earthing switches, designed for indoor and outdoor installations for nominal voltages above 1 000 V and for service frequencies up to and including 60 Hz.
This second edition cancels and replaces the first edition published in 2001, Amendment 1:2011 and Amendment 2:2013. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
  1. new numbering according to IEC 17/1025/RQ to harmonize with ISO/IEC Directives, Part 2, and IEEE Std. C37.100.1;
  2. clause numbering has been aligned with IEC 62271-1:2017;
  3. the Scope has been extended to cover all indoor and outdoor installations. Consideration of switching devices having disconnecting and/or earthing switch functionalities, apart from other functions, are also covered by this document;
  4. ratings have been moved from Annexes B, C and E to Clause 5; the order of the subclauses now corresponds to the order of subclauses in Clause 7;
  5. new rating values for bus-transfer current and bus-transfer voltage have been assigned;
  6. new class of mechanical endurance for earthing switches has been added (M1);
  7. subclause "Rated values of electrical endurance for earthing switches" is now called "Classification of earthing switches for short-circuit making capability";
  8. new subclause with ratings for ice-coating has been added;
  9. new subclause with classification of bus-charging switching capability has been added;
  10. new withstand requirements for interlocking devices have been added;
  11. the way to comply with the requirements of the isolating distance of disconnectors has been modified;
  12. design and construction requirements for position-indicating devices have been modified, aligning the requirements for position indication and signalling;
  13. the value of the operating force has been changed;
  14. the test procedures and validation criteria have been revised and modified where necessary;
  15. requirements for applied voltage during single-phase test on non-simultaneous closing earthing switches have been changed;
  16. non-verifiable requirements have been deleted;
  17. a new subclause has been added for testing mechanical interlocking devices;
  18. the high- and low-temperature test is mandatory if the temperature limits for the service conditions of the apparatus (defined by the manufacturer) are above +40 °C or below −5 °C, and a more detailed testing procedure is given;
  19. the testing procedure to verify the proper functioning of the position-indicating device allows a more practicable testing for every technology used;
  20. a new Annex B has been added with title: "Current-switching capability required of disconnectors and earthing switches";
  21. a new Annex C has been added with title: "Tolerances on test quantities for type tests";
  22. a new Annex E has been added with title: "Extension of validity of type tests".

General Information

Status : ACTIVE
Standard Type: Main
Document No: IEC 62271-102:2018 (EN-FR)
Document Year: 2018
Pages: 222
Edition: 2.0
  • ICS:
  • 29.130.10 High voltage switchgear and controlgear
  • 29.130.99 Other switchgear and controlgear

Life Cycle

Currently Viewing

ACTIVE
IEC 62271-102:2018 (EN-FR)

Related Standards

Knowledge Corner

Expand Your Knowledge and Unlock Your Learning Potential - Your One-Stop Source for Information!

© Copyright 2024 BSB Edge Private Limited.

Enquire now +